Hygiene
Hygiene Meditec™ A C1
Download pdf
Tell a friend
Print
E-tools
Maintenance Guide
System and product description
Installation
Acoustics
Technical properties
System range
Size, mm
600x600
1200x600
T24
•
•
Thickness
15
15
Inst. Diagr.
M255
M255
System and product description
Ecophon Hygiene Meditec A C1 is a wall to wall, sound-absorbing ceiling system intended for environments where disinfection and/or cleaning is required on a regular basis. This system is recommended for dry environments. Examples of applications: nursing and healthcare premises.
The system consists of Ecophon Meditec A tiles, which have a core of high density glass wool utilizing the 3RD Technology and a painted cleanable Akutex™ TH surface. The back of the tile is covered with glass tissue. The edges are primed. The supporting structure is an exposed Ecophon Connect T24 grid of galvanised steel. The weight of the system is approximately 2,5 kg/m². The tiles should be secured to the grid with Connect Universal clips in order to withstand pressure during cleaning and to minimise dirt traps.
M255
M255
VIEW 3D
Drawing Aid
Transitions
Installations
Fixings
Search
See Quantity specification
Arrangement of clips
Suspension with direct bracket
nhys2
Quantity specification (excl. wastage)
Installation diagram (M255) for Ecophon Hygiene Meditec A C1
Size, mm
600x600
1200x600
1 Hygiene Meditec A
2,8/m²
1,4/m²
2 Connect T24 Main runner, installed at 1200 mm centres (max distance from wall 300 mm)
0,9m/m²
0,9m/m²
3 Connect T24 Cross tee, L=1200 mm, installed at 600 mm centres
1,7m/m²
1,7m/m²
4 Connect T24 Cross tee, L=600 mm
0,9m/m²
-
5 Connect Adjustable hanger, installed at 1200 mm centres (max. distance from wall 600 mm)
0,7/m²
0,7/m²
6 Connect Hanger clip
0,7/m²
0,7/m²
7 Connect Universal clip
11/m²
7/m²
8 Alt. Connect Angle trim, fixed c300
as required
as required
9 Alt. Connect Shadow-line trim, fixed c300
as required
as required
10 Connect Inspection hatch C1
as required
as required
11 For direct installation without clip: Connect Direct bracket, installed at 1200 mm centres
0,7/m²
0,7/m²
Δ Min. overall depth of system, with Adjustable hanger and clip: 150 mm, with Direct fixing without clip: 50 mm.
-
-
δ Min. demounting depth: With clip: 150 mm. Without clip: 100 mm.
-
-
Acoustics
Acoustic:
α
p
Practical sound absorption coefficient
Frequency, Hz
—
Ecophon Hygiene Meditec A C1, 200 mm o.d.s.
····
Ecophon Hygiene Meditec A C1, 50 mm o.d.s.
o.d.s= overall depth of system
Sound Absorption:
Test results according to EN ISO 354.
Classification according to EN ISO 11654.
Sound Insulation:
Not applicable
Sound Privacy:
Not applicable
Product
Hygiene Meditec A C1
o.d.s mm
50
200
400
absorption class
C
A
αw
0,70
0,90
NRC
0,8
-
0,85
SAA
0,83
-
0,88
Technical properties
Accessibility:
The tiles are demountable. Minimum demounting depth according to installation diagram. The tiles are secured using clips to allow for effective cleaning. The clips are easily removable from above the ceiling. An easy-to-open Connect Inspection hatch is available to simplify access to the ceiling void.
Cleanability:
Daily dusting and vacuum cleaning. Weekly wet wiping. Steam cleaning four times/year. Can withstand the use of common disinfecting chemicals.
Visual appearance:
White 010, nearest NCS colour sample S 0502-Y, 84% light reflectance.
Influence of climate:
The tiles withstand a permanent ambient RH up to 95% at 30°C without sagging, warping or delaminating (ISO 4611). A higher temperature/moisture is permissible during washing as stated above. Microbiological growth class 0 according to ASTM G 21-96. The grid and accessories meet the demands of corrosion class C1 according to EN ISO 12944-2.
Indoor Climate:
Certified by the Indoor Climate Labelling, emission class M1 for building materials, recommended by the Swedish Asthma and Allergy Association, and can be used in rooms classified as ISO class 5 according to ISO 14644-1.
Environmental influence:
Glass wool core utilizing 3RD Technology. Granted the Nordic Swan eco-label. Fully recyclable.
Fire safety:
The glass wool core of the tiles is tested and classified as non-combustible according to EN ISO 1182. The systems are classified as fire protective covering according to NT FIRE 003.
Country
Standard
Class
Europe
EN 13501-1
A2-s1,d0
Mechanical properties:
See table about Max live load and Min load bearing capacity and Functional demands, Mechanical properties at www.ecophon.com.
Max live load (N)
Min load bearing capacity (N)
M255
, 600x600
50
160
M255
, 1200x600
50
160
Installation:
Installed according to installation diagrams, installation guides and drawing aid. Cut panels must be sealed with Connect sealing tape using the Connect Tape applicator, or Connect Edge sealant. Penetrations must be sealed with a suitable sealant.
Contact us
We can help with technical solutions and answers to your questions about our products or room acoustics.
Read more
Hygiene Premises overview
Hygiene system overview & Quickguide - Room types
Download
Hygiene system brochure.pdf
3D CAD
A new feature turns watching installation diagrams into a 3D experience! Add another dimension to watching our installation diagrams. With our latest innovation we let you twist and turn and view close-ups directly on your computer.
Read more
Copyright © 2002-2013 Ecophon Group. All rights reserved.
Trademarks
Cookies
Disclaimer
Tell a friend
Close
Your friends name:
*
Your friends email:
*
Your name:
*
Your e-mail:
*
Your message:
Transitions
Installation
Fixing
Search
Category
Subcategory
Detail list
Previous image
Next image
Type
Name
Description
Product
Sketch
Result
Previous image
Next image
Close